Single-phase inverter type DXS
Basic use: conversion of DC battery voltage into AC voltage
| TECHNICAL DATA | |
| input voltage | DC 24V – 48V – 110V – 220V, +20%/-15% |
| output voltage | AC 230V ±1%, 50Hz |
| rated power | 0,1kVA – 0,5kVA |
| frequency change | ±0,1% for independent work |
| waveform | sine, THD<4% at linear load |
| dynamic accuracy at 100% load change | ±6% through 1 ms |
| overload | 100% through 5 seconds |
| efficiency | 0,86 – 0,91 at rated conditions, depending on the input voltage and output current |
| cooling | natural |
| protection | output short-circuit - electronic |
| overload-electronic | |
| battery deep discharge | |
| level of mechanical protection | IP 20 |
| dimension | 200 x 90 x 230 mm for 0,1kVA |
| 250 x 127 x 300 mm for 0,5kVA | |
| environment working temperature | 0°C to +40°C |
Sigle phase inverter/rectifier/DC-DC converter type: DXS 48-03B
Device converts 230AC voltage or 48 DC battery voltage into 24VDC or 230VAC. Also can work as 48VDC/24VDC converter.
| TECHNICAL DATA | |
| input voltage | DC 48V or AC 230V (+20%/-15%) |
| output voltage | AC 230V 50Hz (±1,5%) or DC 24V |
| rated power | 0,3kVA |
| frequency change | ±0,1% for independent work |
| waveform | sine, THD<4% at linear load |
| dynamic accuracy at 100% load change | ±6% through 1 ms |
| overload | 100% through 30 seconds |
| efficiency | 0,86 – 0,91 at rated conditions, depending on the input voltage and output current |
| cooling | natural |
| protection | output short-circuit - electronic |
| overload –electronic | |
| battery deep discharge | |
| level of mechanical protection | IP 20 |
| enviroment working temperature | od 0°C to +40°C |
| dimension: | 245 x 120 x 255 mm |
| weight (kg) | 6 kg |
This inveter type is not using grid power in case too deep battery discharge.