Basic use: conversion of DC battery voltage to AC voltage

 

TECHNICAL DATA INVERTER TYPE 3FINV
input voltage DC 60V (+20%/-15%)
output voltage AC 230V 50Hz or 83Hz ( per phase)
rated power 3kVA–12kVA
frequency accuracy ±0,1% for independent work
waveform sine, THD<4% at linear load
overload capability 100% through 30 sec
efficiency 0,86 – 0,91 at rated conditions, depending on the input voltage and output current
cooling forced
protection output short-circuit - electronic
overload
level of mechanical protection IP 20
signalization ON / OFF
stand by
overload
high / low input voltage
blockade of device
environment working temperature 0°C to +40°C

 

3FINV603k-80Hz 3FINV604k-50Hz 3FINV6010k-50Hz 3FINV6012k-50Hz